Product Overview
-
Units are rated in accordance to AHRI Standard 430 whereas the coil performance shall be rated in accordance to AHRI Standard 410.
Double-skin casing with 50mm (2”) 40kg/m3 CFC-Free PU insulation which isolates insulation exposure to the air stream. Wide range of coils offering:
Chilled Water - 1, 2, 3, 4, 5, 6, 7, 8 rows with 8, 10, 12, 14 fin per inch.
Hot Water - 1, 2, 3, 4, 5, 6, 7, 8 rows with 8, 10, 12, 14 fin per inch.
DX Coil - 4 and 6 rows with 8, 10, 12, 14 fin per inch.
All coils are factory pressure tested at 400 psig under water as standard with compressed dry air.
Coil tracks enable easy coil removal for complete cleaning and assurance of a dry unit interior.
Optimized fan impeller size to meet performance criteria:
Features & Benefits
-
Low leak construction with hexagonal socket compression, latch type and nitrile gasket on mating panel parameter.
Options & Accessories
-
Powder painted sloped galvanized steel drain pan with side drainage as standard (optional stainless steel drain pan).
Factory installed unit base of 100mm height, constructed of 14 gauge galvanized steel (optional 125mm height for marine application).
Optional factory supplied Heat Recovery Wheel (HRW) or Horizontal Heatpipe for energy management application.
Optional factory installed UVC lamp. AHU selection software for easy unit selection (please refer to the Carrier’s representative for more details).
39CQM